Skip to specifications
versus.deals
Menu
Browse versus.deals
AIR CONDITIONING & HVAC UNITS

LG ARUN050LMC0

UK configuration

Exact manufacturer unit purpose
MULTI V M, Compressor Unit, Outdoor Unit, 5HP, R410A
Manufacturer heating capacities at separate operating points
14 kW; 16 kW; 54600
Manufacturer cooling capacities at separate operating points
14 kW

LG ARUN050LMC0 in the exact manufacturer-listed UK configuration.

Prices & buying options

Search links open retailer results.

UK: no verified listing yet · checked daily

US: no verified listing yet · checked daily

As an eBay Partner, we may be compensated if you make a purchase.

Affiliate links

We may earn a commission. Search results can include other models; check the exact variant and final price with the retailer.

As an Amazon Associate I earn from qualifying purchases.

Price alert

Email me when the LG ARUN050LMC0 gets cheaper on eBay. We check exact-model listings once a day at 12:00 UTC.

We'll send a link to confirm first.

THE ACTUAL PRODUCT
Front view of MULTI V M, Compressor Unit, Outdoor Unit, 5HP, R410A ARUN050LMC0
Official product image · Image source detailsProduct imagery does not establish a retailer’s bundle or condition.
Compare with LG ZRUN050LSS0

Specifications checked 20 Oct 2026Manufacturer specifications, not a hands-on test.

Options worth comparing

Explore all alternatives

The nearest checked air conditioning & hvac units by key specifications, with what differs from the LG ARUN050LMC0. The first matches the Compare button above.

Front view of MULTI V S, Outdoor Unit, 5HP, R32 ZRUN050LSS0LG ZRUN050LSS0UK manufacturer configuration · ZRUN050LSS0
Exact manufacturer unit purpose
MULTI V S, Outdoor Unit, 5HP, R32This one: MULTI V M, Compressor Unit, Outdoor Unit, 5HP, R410A
Manufacturer efficiency declarations and source methods
EER(Rated) (W/W) 2.86; COP(Rated) (W/W) 4.02; SEER (Wh/Wh) 6.44; SCOP (Wh/Wh) 3.81This one: EER(Rated) (W/W) 2.76; COP(Rated) (W/W) 3.77; SEER (Wh/Wh) 5.26; SCOP (Wh/Wh) 3.85
Front view of MULTI V S, Outdoor Unit, 5HP, R32 ZRUN050GSS0LG ZRUN050GSS0UK manufacturer configuration · ZRUN050GSS0
Exact manufacturer unit purpose
MULTI V S, Outdoor Unit, 5HP, R32This one: MULTI V M, Compressor Unit, Outdoor Unit, 5HP, R410A
Manufacturer efficiency declarations and source methods
EER(Rated) (W/W) 2.86; COP(Rated) (W/W) 4.02; SEER (Wh/Wh) 6.44; SCOP (Wh/Wh) 3.81This one: EER(Rated) (W/W) 2.76; COP(Rated) (W/W) 3.77; SEER (Wh/Wh) 5.26; SCOP (Wh/Wh) 3.85
The useful part.

Key strengths

The official LG UK page identifies manufacturer model ARUN050LMC0.

The checks that matter.

Before you buy

Manufacturer claims do not establish independently measured performance, current retailer stock or price. Unlisted specifications remain explicitly unknown.

Every specification. With its source.

Full specifications

Exact configuration: UK manufacturer configuration · ARUN050LMC0

42 specifications in 6 groups. Values are manufacturer specifications unless a row says “Measured result” or “Calculated from cited specifications”. 5 rows repeat listed facts in the manufacturer’s own wording, kept under “Manufacturer wording”.

Heating, cooling & efficiency

18 items
Manufacturer heating capacities at separate operating points
14 kW; 16 kW; 54600

Each declaration has its own manufacturer operating point, component, measurement method or electrical basis. They are not equivalent unqualified figures. HEATING CAPACITY — Rated (kW): 14; HEATING CAPACITY — Max (kW): 16; HEATING CAPACITY — Max (Btu/h): 54600. Heating/cooling output is separate from electrical consumption and supply. Sound power and sound pressure remain separately labelled in the original rows. No COP/SCOP/EER/SEER conversion, seasonal average or ranking is calculated.

Source
Manufacturer cooling capacities at separate operating points
14 kW

Each declaration has its own manufacturer operating point, component, measurement method or electrical basis. They are not equivalent unqualified figures. COOLING CAPACITY — Rated (kW): 14. Heating/cooling output is separate from electrical consumption and supply. Sound power and sound pressure remain separately labelled in the original rows. No COP/SCOP/EER/SEER conversion, seasonal average or ranking is calculated.

Source
COOLING CAPACITY — Rated (kW)
14Source
HEATING CAPACITY — Rated (kW)
14Source
HEATING CAPACITY — Max (kW)
16Source
HEATING CAPACITY — Max (Btu/h)
54600Source
POWER INPUT(COOLING) — Rated (kW)
5.07Source
COMPRESSOR — Type
ScrollSource
COMPRESSOR — Motor Output (W x No.)
3200 x 1Source
COMPRESSOR — Starting Method
DC Inverter StartingSource
COMPRESSOR — Oil Type
FW68D(PVE)Source
COMPRESSOR — Piston Displacement (cm³/rev)
31.6Source
POWER INPUT(HEATING) — Rated (kW)
3.71Source
EFFICIENCY — EER(Rated) (W/W)
2.76Source
EFFICIENCY — COP(Rated) (W/W)
3.77Source
EFFICIENCY — SEER (Wh/Wh)
5.26Source
EFFICIENCY — SCOP (Wh/Wh)
3.85Source
EFFICIENCY — Pdesign(@-10℃, Heating) (kW)
9.8Source
Manufacturer wording (1)

The same facts in the manufacturer’s combined or original wording, each with its source.

Manufacturer efficiency declarations and source methods
EER(Rated) (W/W) 2.76; COP(Rated) (W/W) 3.77; SEER (Wh/Wh) 5.26; SCOP (Wh/Wh) 3.85

Each declaration has its own manufacturer operating point, component, measurement method or electrical basis. They are not equivalent unqualified figures. EFFICIENCY — EER(Rated) (W/W): 2.76; EFFICIENCY — COP(Rated) (W/W): 3.77; EFFICIENCY — SEER (Wh/Wh): 5.26; EFFICIENCY — SCOP (Wh/Wh): 3.85. Heating/cooling output is separate from electrical consumption and supply. Sound power and sound pressure remain separately labelled in the original rows. No COP/SCOP/EER/SEER conversion, seasonal average or ranking is calculated.

Source

Refrigerant & circuit

5 items
REFRIGERANT — Type
R410ASource
REFRIGERANT — Precharged amount (kg)
2.0Source
REFRIGERANT — GWP(Global Warming Potential)
2087.5Source
REFRIGERANT — t-CO₂ eq.
4.175Source
REFRIGERANT — Control Type
Electronic Expansion ValveSource
Manufacturer wording (1)

The same facts in the manufacturer’s combined or original wording, each with its source.

Manufacturer refrigerant type
R410A; Electronic Expansion Valve

Each declaration has its own manufacturer operating point, component, measurement method or electrical basis. They are not equivalent unqualified figures. REFRIGERANT — Type: R410A; REFRIGERANT — Control Type: Electronic Expansion Valve. Heating/cooling output is separate from electrical consumption and supply. Sound power and sound pressure remain separately labelled in the original rows. No COP/SCOP/EER/SEER conversion, seasonal average or ranking is calculated.

Source

Electrical supply & consumption

1 item
Manufacturer electrical supply requirements
50 Hz 380-415 V 3N~

Each declaration has its own manufacturer operating point, component, measurement method or electrical basis. They are not equivalent unqualified figures. POWER SUPPLY — #1: 50 Hz 380-415 V 3N~. Heating/cooling output is separate from electrical consumption and supply. Sound power and sound pressure remain separately labelled in the original rows. No COP/SCOP/EER/SEER conversion, seasonal average or ranking is calculated.

Source
Manufacturer wording (1)

The same facts in the manufacturer’s combined or original wording, each with its source.

POWER SUPPLY — #1
50 Hz 380-415 V 3N~Source

Installation, dimensions & airflow

14 items
Exact manufacturer unit purpose
MULTI V M, Compressor Unit, Outdoor Unit, 5HP, R410A

Exact manufacturer Product heading. Official current catalogue classes: VRF System. Indoor, outdoor, hydro and whole-package purposes are not substituted for one another.

Source
OUTDOOR FAN — Type
Sirocco FanSource
OUTDOOR FAN — Air Flow Rate(High) (m³/min x No.)
60Source
OUTDOOR FAN MOTOR — Drive
DirectSource
OUTDOOR FAN MOTOR — Output (W x No.)
400 x 2Source
DIMENSIONS — Net(W x H x D) (mm)
580 x 700 x 500Source
DIMENSIONS — Shipping(W x H x D) (mm)
618 x 833 x 564Source
WEIGHT — Net (kg)
69Source
WEIGHT — Shipping (kg)
76Source
EXTERIOR — Color
Morning GraySource
CONNECTING PIPE — Liquid (mm(inch))
Φ9.52 (3/8)Source
CONNECTING PIPE — Gas (mm(inch))
Φ15.88 (5/8)Source
CONNECTABLE INDOOR UNITS NUMBER — Max. (Conditional) (EA)
10Source
HEAT EXCHANGER — Fin Type
Wide Louver PlusSource
Manufacturer wording (1)

The same facts in the manufacturer’s combined or original wording, each with its source.

Manufacturer dimensions and configuration basis
580 x 700 x 500 mm

Original units, axes and stand/component/handle basis retained. No packaging dimension or unstated unit is substituted. Manufacturer section: DIMENSIONS. Source field: Net(W x H x D) (mm).

Source

Operating conditions & sound

3 items
Manufacturer operating ranges and conditions
Not listed by the manufacturer

The captured manufacturer specification table does not list an unambiguous manufacturer operating ranges and conditions. No value is inferred.

Source
SOUND PRESSURE LEVEL (OUTDOOR UNIT) — Cooling / Heating (dB(A))
45 / 45Source
SOUND POWER LEVEL (OUTDOOR UNIT) — Cooling / Heating (dB(A))
68 / 68Source
Manufacturer wording (1)

The same facts in the manufacturer’s combined or original wording, each with its source.

Manufacturer sound declarations and measurement methods
45 / 45; 68 / 68

Each declaration has its own manufacturer operating point, component, measurement method or electrical basis. They are not equivalent unqualified figures. SOUND PRESSURE LEVEL (OUTDOOR UNIT) — Cooling / Heating (dB(A)): 45 / 45; SOUND POWER LEVEL (OUTDOOR UNIT) — Cooling / Heating (dB(A)): 68 / 68. Heating/cooling output is separate from electrical consumption and supply. Sound power and sound pressure remain separately labelled in the original rows. No COP/SCOP/EER/SEER conversion, seasonal average or ranking is calculated.

Source

Controls & supplied items

1 item
CONNECTING CABLE — Communication Cable(VCTF-SB) (mm² × cores)
2C x 1.0 ~ 1.5Source
Similar products.

Compare with another air conditioning & hvac units product

More of the nearest checked air conditioning & hvac units by key specifications, for a side-by-side comparison.